Generator Changeover Switches: Keeping the Power On in Rural Waikato

Kris Goff
7 hours ago
3 min read

Short answer: to run your house off a generator you need a changeover switch wired in at the switchboard by a registered electrician. It physically prevents the generator and the network supply from ever being connected at the same time. Without one you cannot power fixed circuits safely, and back-feeding the network can kill a lineman working to restore your power.

Why a lead into a socket is not a solution

The arrangement people describe as a suicide cord - a lead with plugs on both ends, generator into a wall socket - does two dangerous things. It energises the house wiring through a circuit that is not protected for it, and it pushes power back out through your service line into the network. The transformer down the road steps that back up. Somebody working on what they have isolated as a dead line is then working on a live one. It is illegal, and it is the kind of illegal that kills other people.

What a proper setup looks like

  1. A changeover switch at or next to the switchboard. Manual is fine and is what most rural houses have - you walk out, start the generator, throw the switch.

  2. A generator inlet - a proper external appliance inlet, weatherproof, positioned where you will actually run the generator.

  3. An essential services sub-board, so the generator feeds the circuits that matter rather than trying to carry the whole house.

  4. Earthing done correctly for a portable generator. This is the part most DIY setups get wrong, and it is the part that protects you.

  5. Testing and a Certificate of Compliance. It is fixed wiring, so it is prescribed electrical work.

What to put on the essential circuits

  • Fridge and freezer. The whole reason most people buy a generator.

  • The water pump. On tank or bore supply, no power means no water and no toilet.

  • Lighting to the kitchen, hallway and bathroom.

  • A few sockets for phone charging, the router and a heater.

  • The wood burner fan or a heat pump, if the generator has the capacity.

  • On a farm: the effluent pump and enough of the shed to get through a milking.

Leave off the range, the hot water cylinder and anything with a big motor unless you have specifically sized for them. Motors draw several times their running current at start-up, which is what stalls an undersized generator.

Sizing it

Add up the running load of your essential circuits, then allow headroom for the largest motor starting. A water pump is usually that motor. It is better to have a slightly larger generator and run it lightly loaded than to have one that stalls every time the pump kicks in. We will work out the number with you before you buy - it is a much cheaper conversation than the exchange.

Questions we get asked

Manual or automatic changeover?

Manual for most rural houses - simpler, cheaper, and you are usually home when it matters. Automatic makes sense where the outage cannot be attended, or where something like a freezer room or a farm system cannot wait.

Can I use the generator I already have?

Usually. We check the output, the outlet type, and how it is earthed, then size the inlet and the changeover to suit.

Does it work with solar and a battery?

Different setup, and it depends on the inverter. Some hybrid inverters have their own backup output that does the isolation for you. Tell us what you have got.

How often should I run it?

Start it monthly and run it under load. Generators fail from sitting still far more often than from working.