Thermal Imaging on Switchboards: Finding the Fault Before It Fails
Short answer: a bad electrical connection generates heat before it generates a failure. A thermal imaging camera picks that heat up through a live, loaded board — no shutdown, no dismantling — so the repair gets booked on a Tuesday instead of happening on its own at 2am. For commercial and rural sites it is the highest-value half hour of testing available.
We are based at Waerenga in the North Waikato and cover the Waikato and South Auckland. Registered since 2013, EWRB E 243698.
Why heat is the early warning
Current through a sound connection produces almost no heat. Current through a loose, corroded or undersized connection produces heat in proportion to the resistance — and heat accelerates the corrosion, which raises the resistance, which makes more heat. It is a slow loop that ends in a failed connection, a tripped circuit, a damaged device, or a fire.
The useful part is how long that loop takes. A connection that will fail this summer is usually measurably warm months beforehand. Nothing about the board looks or sounds different. You cannot see it, and you will not find it by looking.
What a scan actually finds
Loose or under-torqued terminations — the single most common find, and the cheapest to fix.
Corroded connections, particularly in wash-down areas, coastal sites and farm sheds.
Unbalanced loading across phases on three-phase boards, which shows as one phase running consistently hotter.
Overloaded circuits that are within their protection rating but working harder than they should.
Failing protective devices — a breaker running hot compared with its neighbours carrying similar load.
Poor connections at the main switch or incomer, where a failure takes out the whole site.
What it does not find, and nobody should pretend otherwise
Thermal imaging is a screening tool, not a complete test.
It needs load. An unloaded board looks perfect. A scan of a shut-down site tells you nothing, which is why it gets done during normal operation.
It does not test earthing, insulation resistance or RCD operation. Those are separate tests and they still have to happen.
It does not see inside sealed equipment — it sees the surface and infers from it.
It reports symptoms, not causes. A hot spot tells you where to open up. It does not tell you why.
It sits alongside periodic inspection and testing rather than replacing it. Periodic verification of an existing installation is covered by AS/NZS 3019, with the Wiring Rules in AS/NZS 3000 behind it.
Who should be having it done
Rural and dairy sheds. Wash-down chemicals, moisture and constant vibration attack terminations. See agricultural electrical services.
Packhouses and coolstores, where a failure mid-season is expensive in a way an office failure is not.
Retail and hospitality, where the board carries heavy continuous load and a shutdown means closing.
Small industrial sites with motor loads and three-phase plant.
Property managers and body corporates responsible for common-area distribution and switchrooms.
Any site where the board grew by accretion and nobody has audited it in a decade.
How a scan runs on a working site
Site runs as normal. We want representative load, so we do not want anything switched off for us.
Covers come off where it is safe to do so, because most enclosures block infrared. This is live work and it is done by a registered electrician with the right controls, not by somebody pointing a camera at a closed door.
Scan and record, comparing components against each other and against expected temperatures for their load.
Report with the images, what was found, and a priority against each item.
Repairs quoted separately. Minor tightening usually gets done on the spot; anything larger gets priced.
Worth doing once, better done on a cycle
A single scan finds what is wrong today. Doing it annually gives you something more useful — a trend. A connection that was two degrees warm last year and eight this year is telling you something a one-off snapshot cannot. That is why it usually sits inside a maintenance agreement rather than being bought ad hoc. See what a maintenance retainer actually covers.
Questions we get asked
Do we have to shut down?
No — the opposite. The scan needs the site running under normal load to be worth anything.
Will my insurer want this?
Some commercial insurers ask about electrical maintenance and testing, and some ask specifically for thermographic surveys on larger installations. Policies differ a lot, so ask yours what it expects rather than assuming. Either way a dated report with images is a good thing to have on file.
How often?
Annually for most commercial sites. More often where the environment is harsh — wash-down areas, dusty packhouses, coastal exposure — because that is where connections degrade fastest.
Is this the same as the electrical certificate?
No. A scan produces a report. Prescribed electrical work produces a Certificate of Compliance. Which document is which is set out in CoC, ESC and RoI.
Can you do it on a house?
We can, but it is rarely the best spend on a domestic board. On a house the higher-value checks are RCD protection and the condition of the board itself — see consumer unit, switchboard or fuse box.
Book a scan
Tell us what the site is, what is on the board and when it runs at full load. Call Kris on 021 466 666, or see the compliance testing page.